Permit Number: F18-1089
Permit Type: Commercial Trade Permit - Alteration Fire
Address: W 5000 INTERNATIONAL AIRPORT RD Anchorage
Location:
Work Description:

FIRE ALARM WITH 2 DEVICES - MJD

CHILD OF C17-2145

Status: Closed
Project Name: CINNABON
Review Type: Fire System
Result: Correction
Result Date: 4/24/2018 2:53:00 PM

Comments:

 Code SectionReview CommentStatus
1_
Circuit N12-21 is overloaded. Plans show 2.01 amps but actual amp draw is 3.132 amps

5 each 757-5A-SS70 15 cd plans show 0.07 amps each, spec sheet shows 0.109 amps each
2 each 757-7A-HS 15/75 cd plans show 0.09 amps each, spec sheet shows 0.150 amps each
10 each 757-3A-SS70 30 cd plans show 0.089 amps each, spec sheet shows 0.130 amps each
3 each 757-8A-SS70 110 cd plans show 0.197 amps each, spec sheet shows 0.329 amps each


2_
Update voltage drop and battery calculations after overload circuit is corrected

3_
Provide Fire Alarm Installation Affidavit



4_
Show floor plans that shows everything connected to BPS N12 -21/22