Work Description: FIRE ALARM WITH 27 DEVICES - MJD
Status: Closed
Project Name: QUICK TURNAROUND FACILITY
Review Type: Fire System
Result: Correction
Result Date: 4/24/2018 11:56:00 AM

Comments:

 Code SectionReview CommentStatus
1_Resolved
Where is this work taking place the plans show 5000 W International Airport Road, the application shows 5960 De Havilland? Update plans or application as applicable


2_Resolved
Provide data/install sheets for the heat detector DT-135wp

3_Resolved
Provide Fire Alarm Installers Affidavit

4_Resolved
What is the ceiling height the detectors are being mounted at?

5_Resolved
Provide heat detector reduced spacing when the ceiling is over 10 feet. 2010 NFPA 72 section 17.6.3.5

6_Resolved
Is there more building than what is being shown on the plans? Google earth show a very large building at location on plans and on application.