Permit Number: C18-1381
Permit Type: Commercial Building Permit - None BldgAlter
Address: 3801 OLD SEWARD HWY Anchorage
Location:
Work Description: Comm T/I to include P/M/E - BWP
Status: Closed
Project Name: PRO NAILS
Review Type: Mechanical
Result: Correction
Result Date: 4/18/2018 8:50:36 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:


Reviewed by: Bergstrom, Leigh W.

Phone: 343-8326

Fax: 249-7615

Email: BergstromLW@muni.org

Permit Manager: Bob Parker

Phone: 343-8391

Email: ParkerRW@muni.org

Project: PRO NAILS

Review Number: 407177


1) STATUS: 4-17-2018 Comments to be addressed.


2) The following comments based upon the 2012 International Building, Mechanical and Fuel Gas Codes must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the IBC, IMC, IFGC or any federal, state or local regulations. 


3) M5                         EF-1 will be exhausting 2,100 CFM during business hours. Clarify the makeup air required per IMC 501.4.


4) M5                         The drying table requires ventilation also. (IMC Table 403.3 footnote "h")


5) M5                         Advisory comment: The main rooms for doing nails require 6/10ths of a CFM of exhaust per square foot of floor area (approximately 770 CFM). This may also include the exhaust at the nail tables.


6) M5                         Clarify the occupancy of the individual back rooms and associated ventilation requirements per IMC 403.3.


7) M5                          Sheet note #2 says there are 11 stations. We only count 10 for 500 CFM total.


8) M5                          The equivalent dryer duct length is well over the maximum 35' allowed per IMC 504.6.4.1.


9) ME-6                       During the cold winter months the metal ducts through the roof will have a tendency to have condensation when not in use due to conduction. (IMC 603.12)


10) When the above comments have been addressed, please update the plans at the MOA Plans Review Office with three sets of revised mechanical pages to include clouded changes, engineers stamp and signature. RE-SUBMITTALS ARE TO BE DIRECTED TO THE ATTENTION OF THE PERMIT MANAGER WITH A LETTER OF RESPONSE ADDRESSING EACH COMMENT.   (23.10.104.8.1)