Electrical Comments
Reviewed by: David Abuobaid Permit#: C18-1381
Phone: 343-8333 Date: 4/17/2018
Fax: 249-7775
Permit Manager: Bob Parker
Phone: 343-8391
Email: Parkerrw@muni.org
Project: Pro Nails (Fax:no fax provided)
___________________________________________________________________________________
1. Thefollowing comments based on the 2014 National Electrical Code (NEC) must beresolved before a permit is issued. The approval of plans and specificationsdoes not permit the violation of any section of the NEC or any federal, stateor local regulations.
2. TRANSFORMERS OVERCURRENT PROTECTION:
Sheet E6. There are twotransformer T1 and T2 that maybe existing. Transformers T1 and T2 feed directlyfrom separate meters and shows and marking “to meter and services”. Please showon the plan the overcurrent protection (on primary and secondary) for thetransformers. Show wiring method and conductor sizes to the primary andsecondary sides.
3. PANELS SCHEDULES:
Sheet E6. Panels 14 and 14A donot show any overcurrent protection for the transformers. Please show panelcalculations with the transformers overcurrent protection and provide the newcalculations.
4. When the above comments have been addressed,please update the electrical plans at the MOA Plans Review Office with three(3) sets of revised electrical pages to include clouded changes, electricalengineers stamp and signature.