Permit Number: C18-1381
Permit Type: Commercial Building Permit - None BldgAlter
Address: 3801 OLD SEWARD HWY Anchorage
Location:
Work Description: Comm T/I to include P/M/E - BWP
Status: Closed
Project Name: PRO NAILS
Review Type: Electrical
Result: Correction
Result Date: 4/17/2018 11:04:31 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:



 Electrical Comments



 



Reviewed by: David Abuobaid                                                Permit
#: C18-1381



Phone: 343-8333                                                                      Date: 4/17/2018



Fax:     249-7775



Permit Manager: Bob Parker



Phone: 343-8391



Email:  Parkerrw@muni.org



Project: Pro Nails (Fax:
no fax provided)                      



___________________________________________________________________________________



1.  The
following comments based on the 2014 National Electrical Code (NEC) must be
resolved before a permit is issued. The approval of plans and specifications
does not permit the violation of any section of the NEC or any federal, state
or local regulations.



 



2.  TRANSFORMERS OVERCURRENT PROTECTION:



Sheet E6. There are two
transformer T1 and T2 that maybe existing. Transformers T1 and T2 feed directly
from separate meters and shows and marking “to meter and services”. Please show
on the plan the overcurrent protection (on primary and secondary) for the
transformers. Show wiring method and conductor sizes to the primary and
secondary sides.



 



3.  PANELS SCHEDULES:



Sheet E6. Panels 14 and 14A do
not show any overcurrent protection for the transformers. Please show panel
calculations with the transformers overcurrent protection and provide the new
calculations.



     



4.  When the above comments have been addressed,
please update the electrical plans at the MOA Plans Review Office with three
(3) sets of revised electrical pages to include clouded changes, electrical
engineers stamp and signature. 



 