Permit Number:
C18-1264
Permit Type:
Commercial Building Permit - None BldgAlter
Address:
E 800 DIMOND BLVD Anchorage
Location:
Work Description:
INSTALLATION OF NEW FIREPLACE AT COMMON AREA IN OPEN CORRIDOR AREA ON SECOND FLOOR BETWEEN DIAMOND NAILS & TREND SETTERS - RED
***FILE ACTIVE- STARTING WORK- 7/8/21 SLO
Status:
Issued
Project Name:
DIMOND CENTER MALL
Review Type:
Fire
Result:
Approved
Result Date:
4/9/2018 2:02:00 PM
Comments:
Code Section
Review Comment
Status
1
_
Resolved
Please provide scaled plan drawings with dimensions.
Reference: IFC Section 105.4.2; AMC 23.10.104.10.1
2
_
Resolved
The framing elevation shown on Sheet F-1 indicates wood framing. Please justify this as the construction type for the project area is Type I-A (part of the tower construction).
Reference: IFC Section 102.4; IBC Section 603.1
3
_
Resolved
Please note on the plans the location(s) and rating(s) of fire extinguisher(s) serving this area. Reference: IFC Section 906.3