TENANT IMPROVEMENT TO INCLUDE P/M/E - RED
NEW SLEEPING ROOMS FOR SLEEP LAB (UP TO 5 INDIVIDUALS AT NO MORE THAN 24HRS STAY AND NOT BEING RENDERED INCAPABLE OF SELF PRESERVATION)
Reviewed by: Bergstrom, Leigh W.
Phone: 343-8326
Fax: 249-7615
Email: BergstromLW@muni.org
Permit Manager: Richard Dienes-Oehm
Phone: 343-8034
Email: Dienes-OehmRE@muni.org
Project: ALASKA REGIONAL MEDICAL - PEAK NEUROLOGY
Review Number: 406530
1) STATUS: 4-05-2018 Comments to be addressed.
2) The following comments based upon the 2012 International Building Code (IBC) must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the IBC or any federal, state or local regulations.
3) A102 The code study indicates that two exits are required. Exit signs are required per IBC 1011 and emergency lighting per IBC 1006.
4) A-201 The 40" mounting height of the 2 mirrors must indicate that the measurement is to the bottom of the reflective surface as required per ICC/ANSI A117.1-603.3.
5) A101 & A201 The ADA water closet clear space is 5 feet from the corner behind the fixture along the back wall towards the sink. It appears that the sink falls within that space. Please clarify.
6) When the above comments have been addressed, please update the plans at the MOA Plans Review Office with three sets of revised architectural pages to include clouded changes, architects stamp and signature. RE-SUBMITTALS ARE TO BE DIRECTED TO THE ATTENTION OF THE PERMIT MANAGER WITH A LETTER OF RESPONSE ADDRESSING EACH COMMENT. (23.10.104.8.1)