Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: F16-1298
Permit Type: Commercial Trade Permit - Alteration Fire
Address: W 320 5TH AVE Anchorage
Location:
Work Description:

5th Avenue Mall master fire alarm upgrade plan. Fire alarm upgrades to common areas. Plan sets also include details for individual tenants, which will be permitted separately.

Fire Alarm (140) devices - AJC

Status: Closed
Project Name: 5TH AVE MALL FIRE ALARM SYSTEM MASTER
Review Type: Fire System
Result: Correction
Result Date: 4/13/2018 9:11:00 AM

Comments:

 Code SectionReview CommentStatus
1_
Project review on hold pending designer changes to strobes do to ceiling heights.

2_
Update cover sheet to show that the scope of the permit/work is for the mall core/common areas only

3_
Add just strobe coverage to cover corridor 107 and 113 correctly

4_
Battery calculations require 15 minutes of alarm time, drawings only show 5 minutes.

5_
There are 4 different model devices listed in the device legend that have strobes associated with them and none of them are listed as a model in the voltage drops. List all the correct devices on each circuit in the voltage drop and battery calculations with the correct amperage.

Models shown:
G4-S7VM
GCF-S7VM
GCF-VM
G1F-VM


6_
Hatch out areas on the drawings that are not part of the scope of work.

7_
Since the drawings and calcs are being modified by ATS Alaska for corrections, an ATS Alaska designer needs to sign the drawings now and not John Wishman. Provide original wet signature on drawings.

8_
Update revision date on front sheet

9_
Plan review stopped - ATS need to review the drawings.




Advisory Information:

ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS