Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: F18-1055
Permit Type: Commercial Trade Permit - Alteration Fire
Address: E 800 DIMOND BLVD Anchorage
Location:
Work Description:

SPACE 191.  TENANT BUILDOUT/ IMPROVEMENT FOR NEW TENANT BATH AND BODY WORKS - MJD

New Fire Alarm - 10 Devices - BWP

Status: Closed
Project Name: Child of Bldg App C17-2005
Review Type: Fire System
Result: Approved
Result Date: 4/2/2018 11:40:00 AM

Comments:

 Code SectionReview CommentStatus
1_Resolved
HPF24S8 power supply battery calculations show only 5 minutes of alarm time, voice evac requires 15 minutes of alarm time.

2_Resolved
HPF24S8 power draw one lines do not match the calc sheets, device counts are different and device candelas are different.

3_Resolved
Show entire floor plan served by BPS HPF24S8




Advisory Information:

ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter