Permit Number: C18-1264
Permit Type: Commercial Building Permit - None BldgAlter
Address: E 800 DIMOND BLVD Anchorage
Location:
Work Description: INSTALLATION OF NEW FIREPLACE AT COMMON AREA IN OPEN CORRIDOR AREA ON SECOND FLOOR BETWEEN DIAMOND NAILS & TREND SETTERS - RED
***FILE ACTIVE- STARTING WORK- 7/8/21 SLO
Status: Issued
Project Name: DIMOND CENTER MALL
Review Type: Mechanical
Result: Correction
Result Date: 3/29/2018 8:20:26 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:


Reviewed by: Bergstrom, Leigh W.


Phone: 343-8326

Fax: 249-7615

Email: BergstromLW@muni.org

Permit Manager: Richard Dienes-Oehm

Phone: 343-8034

Email: Dienes-OehmRE@muni.org

Project: DIMOND CENTER MALL

Review Number: 405793


1) STATUS: 3-29-2018 Comments to be addressed.


2) The following comments based upon the 2012 International Building, Mechanical and Fuel Gas Codes must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the IBC, IMC, IFGC or any federal, state or local regulations. 


3) Provide structural and seismic calculations plus fastening details for FP-1 to include the engineers stamp and signature for structural review on a deferred submittal basis.


4) Clarify a secure access to FP-1 for "inspection, service, repair and replacement without ....... removing permanent construction ....." (IMC 306.1)


5) When the above comments have been addressed, please update the plans at the MOA Plans Review Office with three sets of revised mechanical pages to include clouded changes, engineers stamp and signature. RE-SUBMITTALS ARE TO BE DIRECTED TO THE ATTENTION OF THE PERMIT MANAGER WITH A LETTER OF RESPONSE ADDRESSING EACH COMMENT.   (23.10.104.8.1)


 