Permit Number: C18-1264
Permit Type: Commercial Building Permit - None BldgAlter
Address: E 800 DIMOND BLVD Anchorage
Location:
Work Description: INSTALLATION OF NEW FIREPLACE AT COMMON AREA IN OPEN CORRIDOR AREA ON SECOND FLOOR BETWEEN DIAMOND NAILS & TREND SETTERS - RED
***FILE ACTIVE- STARTING WORK- 7/8/21 SLO
Status: Issued
Project Name: DIMOND CENTER MALL
Review Type: Fire
Result: Correction
Result Date: 4/5/2018 7:11:14 AM

Comments:

 Code SectionReview CommentStatus
1_
Please provide scaled plan drawings with dimensions.
Reference: IFC Section 105.4.2; AMC 23.10.104.10.1


2_
The framing elevation shown on Sheet F-1 indicates wood framing. Please justify this as the construction type for the project area is Type I-A (part of the tower construction).
Reference: IFC Section 102.4; IBC Section 603.1


3_
Please note on the plans the location(s) and rating(s) of fire extinguisher(s) serving this area. Reference: IFC Section 906.3