Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: X18-1132
Permit Type: Commercial Building Permit - ChangeOrdr BldgAlter
Address: E 790 DIMOND BLVD Anchorage
Location:
Work Description: ARCHITECTURAL INTERIOR IMPROVEMENTS.  AE
Status: Closed
Project Name: Change Order of Bldg App C17-1087
Review Type: Plumbing
Result: Correction
Result Date: 2/27/2018 9:28:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:


Reviewed by: Bergstrom, Leigh W.

Phone: 343-8326

Fax: 249-7615

Email: BergstromLW@muni.org

Permit Manager: Melissa Davidson

Phone: 343-8339

Email: DavidsonMJ@muni.org

Project: DIMOND INTERMODAL FACILITY #C17-1087

Review Number: 404777


1) STATUS: 2-27-2018 Comments to be addressed.


2) The following comments based upon the 2012 Uniform Plumbing Code must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the Uniform Plumbing Code or any federal, state or local regulations.


3) M100                       On the Plumbing Fixture Schedule please clarify notes #1 and #2.


4) M100                       FD-1 requires trap seal protection per UPC 1007.


5) M101                         Food Service Plan K1 indicates that there are two Fryers #13. Please clarify quantity and BTU input for each unit.


6) M300                         There was no schedule of fixtures P-1 thru P-4 on M100. Please clarify.


7) M301                         The 3/4" gas branch to WH-1 (199 MBH @ 45 feet) and the 3/4" gas branch to K14 (159 MBH @ 55 feet) appear to be undersized per UPC Table 1216.2(1).


8) When the above comments have been addressed, please update the plans at the MOA Plans Review Office with three sets of revised plumbing pages to include clouded changes, engineers stamp and signature. RE-SUBMITTALS ARE TO BE DIRECTED TO THE ATTENTION OF THE PERMIT MANAGER WITH A LETTER OF RESPONSE ADDRESSING EACH COMMENT.   (23.10.104.8.1)

ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter