Permit Number: X18-1131
Permit Type: Commercial Building Permit - ChangeOrdr BldgCombo
Address: 1700 HILLCREST DR Anchorage
Location:
Work Description: INCLUDED FOR REVIEW ARE (2) COPIES OF THE APPROVED ALUMINUM STOREFRONT SUBMITTAL FOR THE WEST/ROMIG IMC RENOVATION PROJECT.  SAME A S X18-1040, EXCEPT THE ADDED INTERIOR SEISMIC CALCS IN APPENDIX B AND THE HORIZONTAL MULLIONS ON THE SHOP DRAWINGS PER RFI-122.  AE
Status: Closed
Project Name: Change Order of Bldg App C17-1344
Review Type: Structural
Result: Correction
Result Date: 3/21/2018 10:36:21 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

DEFERRED SUBMITTAL STATUS
3/21/2018 - Deferred submittal reviewed. Comments issued.

1. Please provide drawings with text that is at least 3/32" tall as required by MOA policy AG.39.

2. Please provide drawings that are stamped by an engineer licensed in Alaska as required by the Alaska State Statutes section 08.48.221.


3. Reference the details on sheet 5.23. There is a note in these details that indicates to "fasten as required." Please provide the actual fastening requirements.

4. Please provide confirmation that the engineer of records comment was addressed. The comment is "Confirm that roof structure deflection is accommodated at interior storefront."