Permit Number: C17-2052
Permit Type: Commercial Building Permit - None BldgAlter
Address: 1700 HILLCREST DR Anchorage
Location:
Work Description: HVAC UPGRADE FOR THE GYM AND AUDITORIUM MECHANICAL ROOMS AT WEST HIGH SCHOOL - MJD
Status: Closed
Project Name: WEST HS GYM & AUDITORIUM HVAC
Review Type: Architectural
Result: Approved
Result Date: 1/11/2018 2:12:00 PM

Comments:

 Code SectionReview CommentStatus
1_Resolved
Please revise/update the code analysis reclassification for West High School Auditorium and Gymnasium areas per 2012 ICC construction type to VA and co-ordinate with Mechanical.

2_Resolved

Drawing G103, Code Study; The frontage increase for the auditorium is shown as .45 and also as .42.  Per the Architect of Record, .42 will be used and the allowable area recalculated.  This was redlined on the plans and results in no adverse effect on the results of this code change.





3_Resolved

Drawing A2 and A11 indicate Intumescent Coatings are required. Verify that the Intumescent Coating is suitable for this use per the manufacturers listing.  Special Inspection is required for Intumescent Coatings; thus, submit the manufacturers listing for the Intumescent Coating and a Special Inspection Letter for this application on a deferred submittal basis.