Permit Number:
C17-2052
Permit Type:
Commercial Building Permit - None BldgAlter
Address:
1700 HILLCREST DR Anchorage
Location:
Work Description:
HVAC UPGRADE FOR THE GYM AND AUDITORIUM MECHANICAL ROOMS AT WEST HIGH SCHOOL - MJD
Status:
Closed
Project Name:
WEST HS GYM & AUDITORIUM HVAC
Review Type:
Structural
Result:
Correction
Result Date:
1/18/2018 9:48:31 AM
Comments:
Code Section
Review Comment
Status
Advisory Information:
PERMIT STATUS
12/5/2017 - Permit reviewed. Comments issued.
1. Reference page 61 of the calculations. Please justify the used of R=4 for the concrete shear walls. IEBC section 301.1.4.1(1) requires structural systems to be classified as Ordinary unless it can be shown that the system meets the requirements of "Intermediate" or "Special."
Comment resolved. This was an error by the reviewer as Ordinary Plain Concrete Walls has a lower R value. WAB - 1/17/2018
2. Reference the calculations. The design of the floor and wall infills could not be located. Please provide. Please note that this may include checks of the jams and headers in the existing opening. Reference the Anchorage Administrative Code (AAC) section 23.10.104.8.
Comment remains. It appears that it has been assumed that the infills are simply supported. This means the edges of the openings need to be checked for the additional loading they now supporting tributary weight or lateral loads from the infill. The anchorage of the infill to the existing needs to be verified as well as the capacity of post installed rebar in the direction fo the thickness of the wall could be extremely limited. WAB - 1/18/2018
3. Reference details 6 and 10 on sheet S-501. Please give maximum opening sizes the details can be applied to. Reference AAC section 23.10.104.8.
Comment resolved. This has been provided. WAB - 1/18/2018
4. Please provide a letter from the Owner indicating who they are hiring to provide special inspectors for this project. The special inspectors must be licensed by MOA in the types of inspections to be performed. Reference IBC section 1703.1.
Comment remains. This does not appear to have been provided. WAB - 1/18/2018