Permit Number: C17-2145
Permit Type: Commercial Building Permit - None BldgAlter
Address: W 5000 INTERNATIONAL AIRPORT RD Anchorage
Location:
Work Description: TI TO INCLUDE DEMO EXISTING TENANT IMPROVEMENTS, NEW WALLS, CEILINGS, FINISHES.  PLUMBING, MECHANICAL AND ELECTRICAL MODIFICATIONS.  CREAM, CINNABON, PORK AND PICKLE - MJD
Status: Closed
Project Name: CINNABON, PORK AND PICKLE, CREAM
Review Type: Structural
Result: Correction
Result Date: 12/14/2017 8:41:47 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:


Reviewed by: Grant Gephardt                                                   

Phone: 343-8081                                                                       

Email: GephardtGC@muni.org

 

Permit Manager: Melissa Davidson

Phone: 343-8339

Email: DavidsonMJ@muni.org

 

Permit #: C17-2145

Project: Cinnabon, Pork & Pickle, Cream

Review Number: 402093

Date: 2017 December 14

____________________________________________________________________________________

 

PERMIT STATUS

12/11/2017 – Initial review complete. Comments issued.

12/14/2017 – Resubmittal review complete. Updated comments in bold.

 

 

ADVISORY COMMENT (NO RESPONSE REQUIRED) 

This review is based on the requirements of the Anchorage Municipal Code (AMC), 2012 International Building Code (IBC), 2012 International Residential Code (IRC) and all adopted references thereto as amended by MOA. The following comments must be addressed before a permit can be issued. The approval of plans and specifications does not permit the violation of the codes, or any federal, state or local regulations.

 

 

1. CALCULATIONS

Please provide structural calculations demonstrating the new framing conditions are adequate.

[Reference: IBC 2012 § 1604.4]

 

              12/14/2017 – Comment resolved. Calculations provided.

 

2. NEW BEARING WALL

a. Please clarify whether the studs in the new bearing wall align with the existing joists above.

[Reference: AISI S200-07 § C4.3.3]

 

b. It appears there is a header over an opening at the north end of the wall. Please specify the construction of the header.

[Reference: IBC 2012 § 1603.1]

 

              12/14/2017 – Comment 2a and 2b remain.

 

3. PARTITION WALLS

Light-framed partition walls over 9 feet tall need to be braced to the structure for seismic loads. It appears there are new walls included in this project that trigger this requirement. Please provide a detail for this condition on the Architectural or Structural plans.

[Reference: ASCE 7-10 § 13.5.8]

 

              12/14/2017 – Comment remains.