Permit Number: C17-2145
Permit Type: Commercial Building Permit - None BldgAlter
Address: W 5000 INTERNATIONAL AIRPORT RD Anchorage
Location:
Work Description: TI TO INCLUDE DEMO EXISTING TENANT IMPROVEMENTS, NEW WALLS, CEILINGS, FINISHES.  PLUMBING, MECHANICAL AND ELECTRICAL MODIFICATIONS.  CREAM, CINNABON, PORK AND PICKLE - MJD
Status: Closed
Project Name: CINNABON, PORK AND PICKLE, CREAM
Review Type: Plumbing
Result: Correction
Result Date: 12/11/2017 9:57:15 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:


Reviewed by: Bergstrom, Leigh W.

Phone: 343-8326

Fax: 249-7615

Email: BergstromLW@muni.org

Permit Manager: Melissa Davidson

Phone: 343-8339

Email: DavidsonMJ@muni.org

Project: CINNANON, PORK & PICKLE

Review Number: 401797


1) STATUS: 12-11-2017 Comments to be addressed.


2) The following comments based upon the 2012 Uniform Plumbing Code must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the Uniform Plumbing Code or any federal, state or local regulations. 


3) M2.0 & M2.1                   FS-1 adjacent to C219 serves beverage dispenser C218. The cast iron waste piping specified is not compatible with the byproducts disposed of at a beer or soda dispenser. (UPC 312.4)


4) 2/M2.2                             Food service drawings FS2 & FS2.1 indicate 3 each 1-1/2" waste outlets for the 3-compartment sinks. Please clarify.


5) When the above comments have been addressed, please update the plans at the MOA Plans Review Office with three sets of revised plumbing pages to include clouded changes, engineers stamp and signature. RE-SUBMITTALS ARE TO BE DIRECTED TO THE ATTENTION OF THE PERMIT MANAGER WITH A LETTER OF RESPONSE ADDRESSING EACH COMMENT.   (23.10.104.8.1)