Register
My Neighborhood
Jobs
Contact Us
Home
Residents
Businesses
Government
Visitors
Departments
Public Safety
Transportation
Recreation
ePay
Maps
Services A-Z
Muni.org
>
Departments
>
Development Services
> Permit Information & Inspection Request
Click Here To Go Back To Permit Information
Permit Number:
F17-1244
Permit Type:
Commercial Trade Permit - Alteration Fire
Address:
1700 HILLCREST DR Anchorage
Location:
Work Description:
RENOVATION OF AN ADDITION TO IMC WING. RECONFIGURATION OF WHS ADMIN AREA. THIS APPLICATION IS FOR DEMOLITION, HAZMAT, FOOTINGS, FOUNDATIONS, SITE WORK PERMIT AND EARLY STRUCTRUAL REVIEW AS AGREE ON WITH THE MOA DURING MEETING 3/8/17. COMPLETED PLANS TO BE SUBMITTED FOR COMPLETE BUILDING PERMIT IN MAY. FULL PAYMENT FOR THE COMPLETED BUILDING PERMIT IS BEING MADE AT THIS TIME TO SIMPLIFY THE APPLICATION AND REVIEW PROCESS. AE
Status:
Closed
Project Name:
Child of Bldg App C17-1344
Review Type:
Fire System
Result:
Approved
Result Date:
11/27/2017 2:40:00 PM
Comments:
Code Section
Review Comment
Status
1
_
Resolved
Provide code compliant seismic bracing and hanging per 2010 NFPA 13 chapter 9 on new existing piping in the work area. 2012 IBC 903.2.3, 903.3.1.1, 2012 IEBC 804.2.2
2
_
Resolved
Provide lateral sway bracing calculations for the zone of influence or specific table with pipe length per 2010 NFPA 13 section 9.3.5.3.
Advisory Information:
ADA Compliance
Privacy Statement & Disclaimer
Employee Search
eNewsletter
RSS
OFFICIAL WEB SITE OF THE MUNICIPALITY OF ANCHORAGE, ALASKA
632 West 6th Avenue, Anchorage, Alaska 99501