Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: F17-1239
Permit Type: Commercial Trade Permit - Alteration Fire
Address: E 800 DIMOND BLVD Anchorage
Location:
Work Description: FIRE SPRINKLER - 530 DEVICES - RED
Status: Closed
Project Name: Child of Bldg App C17-1119
Review Type: Fire System
Result: Correction
Result Date: 11/20/2017 12:55:00 PM

Comments:

 Code SectionReview CommentStatus
1_Resolved
Plans are being replaced with new set. Do not review until re-submittal

2_Resolved
Provide sprinkler drawings for areas with raised floors with concealed combustible construction. Provide separate sheet for this area of coverage

3_Resolved
Show locations and walls of coolers and freezers

4_Resolved
Missing heads on FP2 in front of exterior stairs exit through the top of the page to the right of the flex loops. - picture to be emailed

5_Resolved
show areas with drop ceiling with ceiling grid lay out and show sprinkler heads above drop ceilings with combustible construction.

6_Resolved
Printed plans are not to scale, provide new plans

7_Resolved
Provide SCALE BAR on all sheets

8_Resolved
Update head legend on all sheets to show all heads

9_Resolved
Provide grid lines that match. example sheet 3 from left to right start at 10 in the middle it 15.1 and restarts at 39 and ends at 26. Sheet 2 grid lines are incomplete.

10_Resolved
Provide hanger detail for hanging in wood construction



11_Resolved
provide end on line restraint detail

12_Resolved
No FDC connection provided to the Dave and Busters riser. Provide connection to the main mall FDC interconnected piping. 2010 NFPA 13 section 8.17.2.4.3

13_Resolved
Kitchen area has combustible construction above the drop ceiling provide sprinkler protection.




Advisory Information:

ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter