Permit Number: C17-2052
Permit Type: Commercial Building Permit - None BldgAlter
Address: 1700 HILLCREST DR Anchorage
Location:
Work Description: HVAC UPGRADE FOR THE GYM AND AUDITORIUM MECHANICAL ROOMS AT WEST HIGH SCHOOL - MJD
Status: Closed
Project Name: WEST HS GYM & AUDITORIUM HVAC
Review Type: Structural
Result: Correction
Result Date: 12/5/2017 10:50:08 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

PERMIT STATUS
12/5/2017 - Permit reviewed. Comments issued.

1. Reference page 61 of the calculations. Please justify the used of R=4 for the concrete shear walls. IEBC section 301.1.4.1(1) requires structural systems to be classified as Ordinary unless it can be shown that the system meets the requirements of "Intermediate" or "Special."

2. Reference the calculations. The design of the floor and wall infills could not be located. Please provide. Please note that this may include checks of the jams and headers in the existing opening. Reference the Anchorage Administrative Code (AAC) section 23.10.104.8.

3. Reference details 6 and 10 on sheet S-501. Please give maximum opening sizes the details can be applied to. Reference AAC section 23.10.104.8.

4. Please provide a letter from the Owner indicating who they are hiring to provide special inspectors for this project. The special inspectors must be licensed by MOA in the types of inspections to be performed. Reference IBC section 1703.1.