Reviewed by: Grant Gephardt
Phone: 343-8081
Email: GephardtGC@muni.org
Permit Manager: Melissa Davidson
Phone: 343-8339
Email: DavidsonMJ@muni.org
Permit #: C17-2006
Project: Ted Stevens Airport Site #136
Review Number: 400239
Date: 2017 November 7
____________________________________________________________________________________
PERMIT STATUS
11/07/2017 – Initial review complete. Comments issued.
1. CALCULATIONS
The seismic load case on the component also requires a concurrent vertical force of ±0.2SDSWp to be considered. Please revise or clarify.
[Reference: ASCE 7-10 § 13.3.1]
2. EXISTING STRUCTURE
It’s not clear what the existing floor structure is or if this is alteration is resulting in an increase of loads to the framing. Please clarify.
[Reference: IEBC 2012 § 403.3, AMC § 23.65.403.3]
Please provide a written response to the comments and include one copy of additional or revise calculations, and two copies of additional or revised drawings. While not required it is extremely helpful to the reviewer if the response indicates where in the submittal each comments has been addressed.
All submittals should be sent to the permit manager.