Permit Number:
F17-1239
Permit Type:
Commercial Trade Permit - Alteration Fire
Address:
E 800 DIMOND BLVD Anchorage
Location:
Work Description:
FIRE SPRINKLER - 530 DEVICES - RED
Status:
Closed
Project Name:
Child of Bldg App C17-1119
Review Type:
Fire System
Result:
Correction
Result Date:
11/7/2017 9:30:00 AM
Comments:
Code Section
Review Comment
Status
1
_
Resolved
Plans are being replaced with new set. Do not review until re-submittal
2
_
Provide sprinkler drawings for areas with raised floors with concealed combustible construction. Provide separate sheet for this area of coverage
3
_
Show locations and walls of coolers and freezers
4
_
Missing heads on FP2 in front of exterior stairs exit through the top of the page to the right of the flex loops. - picture to be emailed
5
_
show areas with drop ceiling with ceiling grid lay out and show sprinkler heads above drop ceilings with combustible construction.
6
_
Printed plans are not to scale, provide new plans
7
_
Provide SCALE BAR on all sheets
8
_
Update head legend on all sheets to show all heads
9
_
Provide grid lines that match. example sheet 3 from left to right start at 10 in the middle it 15.1 and restarts at 39 and ends at 26. Sheet 2 grid lines are incomplete.
10
_
Provide hanger detail for hanging in wood construction
11
_
provide end on line restraint detail