Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: C17-1961
Permit Type: Commercial Building Permit - None BldgAlter
Address: E 401 6TH AVE Anchorage
Location:
Work Description: GUESTROOM AND LOBBY RENOVATION. FINISHES ON ALL FLOORS. ALL ROOMS REMODELED.  TO INCLUDE ELECTRICAL (ADDING OUTLET IN EACH ROOM).  AE
Status: Closed
Project Name: SHERATON ANCHORAGE HOTEL AND SPA REMODEL
Review Type: Fire
Result: Correction
Result Date: 11/2/2017 7:10:13 AM

Comments:

 Code SectionReview CommentStatus
1_Resolved
Please verify the continuity of the shafts for the elevators and the laundry chute. Note that a termination room for the laundry chute may not be required; a rated opening protective (e.g. 1-hour hatch/door assembly) will be required.
Reference: IFC Section 1103.4.3

11/2/17 - Resolved. Comment acknowledged // PANILO


2_Resolved
Per maintenance inspection, some of the elevator lobby doors are damaged to where it may not meet the requirements for the 90-minute fire-resistance rating. Please coordinate replacement and/or repairs. If repairs are made, such repairs must be in compliance with NFPA 80
Reference: IFC Section 703.2, 1103.4.3

11/2/17 - Resolved. Comment acknowledged // PANILO


3_
Refer to Sheet I-113. The exiting from the most remote point of Room 1513 to the south stair is greater than 75 ft. The doors to the meeting/dining room to the west are locked under normal operations and only release under fire alarm. A second exit is required. Please clarify the exiting from this level.
Reference: IFC Section 1104.18

11/2/17 - Not resolved. Response notes there is an agreement between Remington and AFD regarding the allowance of the single exit space. No record of this agreement was found in AFD files, nor any recollection by any of the inspectors who have been involved with the hotel. Please clarify exiting as requested above.





Advisory Information:

ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS