Permit Number: C17-2005
Permit Type: Commercial Building Permit - None BldgAlter
Address: E 800 DIMOND BLVD Anchorage
Location:
Work Description:

SPACE 191.  TENANT BUILDOUT/ IMPROVEMENT FOR NEW TENANT BATH AND BODY WORKS - MJD

CONTRACTOR TO PAY FOR INSPECTIONS PRIOR TO ISSUING PERMIT

CONTRACTOR PAID FOR 8 INSPECTIONS ON 1/26/18.  AE

CONTRACTOR PAID FOR 8 ADDITIONAL INSPECTIONS ON 3/7/18. AE


Status: Closed
Project Name: BATH AND BODY WORKS
Review Type: Electrical
Result: Correction
Result Date: 10/30/2017 1:45:07 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:



Electrical Comments



 



Reviewed by: David Abuobaid                                                Permit
#: C17-2005



Phone: 343-8333                                                                      Date 10/30/2017              



Fax:     249-7775                                                                     



Email:  AbuobaidDH@muni.org



Permit Manager: Melissa Davidson



Phone: 343-8339



Email:  Pdavidsonmj@muni.org



Project: Bath &
Body Works (Fax: no fax #)



____________________________________________________________________________________  

1. The following comments based on
the 2014 National Electrical Code (NEC) must be resolved before a permit is
issued. The approval of plans and specifications does not permit the violation
of any section of the NEC or any federal, state or local regulations.



 



2.  CIRCUIT DIRECTORY OR CIRCUIT INDENTIFICATION
ON FLOOR PLAN & PANEL SCHEDULES:



Sheet E05.01 (Panel
Schedules and Floor Plans Circuit Identifications). Panel schedules have many
circuits named BBW cabinet LTG, Sales center LGT, BBW cashwrap REC. Please note
that these circuits should be individually identified with their locations on
floor plans and on the panel schedules according to NEC 408.4 for circuit
identifications.



 



3.  TRANSFORMERS MOUNTING (STRUCTURAL REVIEW)



Sheet E05.01 (Transformers Structural Seismic
Calculations). Is the transformer part of the listed switchgear?



Provide structural, seismic calculations and fastening
details for the transformer including engineers stamp and signature, for
structural review on a deferred submittal basis.
Refer
to Anchorage
Administrative Code AAC 23.10.104.8.1. Please address.



 



4.  TRANSFORMER
DISCONNECTING MEANS:



Sheet E05.01 (Transformers disconnecting means
location). Is the transformer part of the listed switchgear?



The disconnecting means should be within sight
and readily accessible as required by NEC Section 629.51(c).
Please address.



 



5.  AMPERAGE INTERRUPTING CAPACITY:



Sheet E05.01 (Panel Schedule Amperage
Interrupting Capacity). Panel schedules AIC are 65,000 Amps. Please provide
detail AIC calculation for any panel has AIC rating higher than 10,000A.



 



6. AVAILABLE FAULT CURRENT:



Sheet E05.01 (Available Fault Current
- Panel Schedules and Line Diagram). Provide calculation for the available
fault current at the main service equipment. NEC Section 110.24 requires that
service equipment be legibly marked in the field with maximum available fault
current. Please address.



 



7. When the above comments have been addressed,
please update the electrical plans at the MOA



Plans Review Office with three (3) sets of
revised electrical pages to include clouded changes, electrical engineers stamp
and signature. 



 



 



 



 