Permit Number: C17-2005
Permit Type: Commercial Building Permit - None BldgAlter
Address: E 800 DIMOND BLVD Anchorage
Location:
Work Description:

SPACE 191.  TENANT BUILDOUT/ IMPROVEMENT FOR NEW TENANT BATH AND BODY WORKS - MJD

CONTRACTOR TO PAY FOR INSPECTIONS PRIOR TO ISSUING PERMIT

CONTRACTOR PAID FOR 8 INSPECTIONS ON 1/26/18.  AE

CONTRACTOR PAID FOR 8 ADDITIONAL INSPECTIONS ON 3/7/18. AE


Status: Closed
Project Name: BATH AND BODY WORKS
Review Type: Architectural
Result: Correction
Result Date: 10/27/2017 4:18:07 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:



Reviewed by: Bergstrom, Leigh W.

Phone: 343-8326

Fax: 249-7615

Email: BergstromLW@muni.org

Permit Manager: Melissa Davidson

Phone: 343-8339

Email: DavidsonMJ@muni.org

Project: BATH AND BODY WORKS

Review Number: 399708



1) STATUS: 10-27-2017 Comments to be addressed.


2) The following comments based upon the 2012 International Building Code (IBC) must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the IBC or any federal, state or local regulations.


3) A00.0 Key Plan                             This installation is apparently at ground level and this major part of the Dimond Center Mall has no basement. Please clarify "Level 2 of 3".


4) A00.0 Construction Type              This major part of the Dimond Center Mall has been determined to be Type "III-B" construction. (For future reference the Tower at the south east part of the mall is Type "I-A" construction.)


5) A00.0 Travel Distance                   The maximum allowable travel distance for an "M" occupancy with sprinklers is 250 feet per IBC Table 1016.2.


6) When the above comments have been addressed, please update the plans at the MOA Plans Review Office with three sets of revised architectural pages to include clouded changes, architects stamp and signature. RE-SUBMITTALS ARE TO BE DIRECTED TO THE ATTENTION OF THE PERMIT MANAGER WITH A LETTER OF RESPONSE ADDRESSING EACH COMMENT.   (23.10.104.8.1)