Permit Number: C17-1961
Permit Type: Commercial Building Permit - None BldgAlter
Address: E 401 6TH AVE Anchorage
Location:
Work Description: GUESTROOM AND LOBBY RENOVATION. FINISHES ON ALL FLOORS. ALL ROOMS REMODELED.  TO INCLUDE ELECTRICAL (ADDING OUTLET IN EACH ROOM).  AE
Status: Closed
Project Name: SHERATON ANCHORAGE HOTEL AND SPA REMODEL
Review Type: Fire
Result: Correction
Result Date: 10/23/2017 9:22:35 AM

Comments:

 Code SectionReview CommentStatus
1_
Please verify the continuity of the shafts for the elevators and the laundry chute. Note that a termination room for the laundry chute may not be required; a rated opening protective (e.g. 1-hour hatch/door assembly) will be required.
Reference: IFC Section 1103.4.3


2_
Per maintenance inspection, some of the elevator lobby doors are damaged to where it may not meet the requirements for the 90-minute fire-resistance rating. Please coordinate replacement and/or repairs. If repairs are made, such repairs must be in compliance with NFPA 80
Reference: IFC Section 703.2, 1103.4.3


3_
Refer to Sheet I-113. The exiting from the most remote point of Room 1513 to the south stair is greater than 75 ft. The doors to the meeting/dining room to the west are locked under normal operations and only release under fire alarm. A second exit is required. Please clarify the exiting from this level.
Reference: IFC Section 1104.18





Advisory Information:

Fire review will be signed off pending acknowledgement of items 1 and 2 in the comments above. Comment 3 must be resolved for sign off // PANILO