Electrical Comments
Reviewed by: David Abuobaid Permit#s: C17-17891 and C17-1892
Phone: 343-8333 Date: 9/15/2017
Fax: 249-7775
Email: AbuobaidDH@muni.org
Permit Manager: Bob Parker
Phone: 343-8391
Email: Parkerrw@muni.org
Project: Spirit Site #AK68X2007 (Fax: 907-349-0101)
Spirit Site #AK68C015
____________________________________________________________________________________ REQUIREMENT OF ELECTRICAL SCOPE OFWORK:
The plans are stamped and signed by the civil engineer.
Please provide 100% designed engineered drawing by aregistered professional electrical engineer of the State of Alaska. The designshall include floor plans, wiring method, home run wiring with type, size ofwires and conduits, over-current protection, accessibility to over-currentprotection, existing service load calculations, panel schedules with connected anddemand loads and one-line diagram.