Permit Number:
C17-1961
Permit Type:
Commercial Building Permit - None BldgAlter
Address:
E 401 6TH AVE Anchorage
Location:
Work Description:
GUESTROOM AND LOBBY RENOVATION. FINISHES ON ALL FLOORS. ALL ROOMS REMODELED. TO INCLUDE ELECTRICAL (ADDING OUTLET IN EACH ROOM). AE
Status:
Closed
Project Name:
SHERATON ANCHORAGE HOTEL AND SPA REMODEL
Review Type:
Architectural
Result:
Correction
Result Date:
10/12/2017 8:48:00 AM
Comments:
Code Section
Review Comment
Status
1
_
The code study indicates that the project is a level 1 alteration to chapter 7 of the IEBC. However, the plans Drawing I-114 indicates the removal of several connector doors between rooms on the 6th and 7th floors. Thus, for at least for the 6th and 7th floors, the project is a level 2 alteration to chapter 8 of the IEBC to include both chapter 7 and 8 of the IEBC.
Advisory Information: