Permit Number:
F17-1244
Permit Type:
Commercial Trade Permit - Alteration Fire
Address:
1700 HILLCREST DR Anchorage
Location:
Work Description:
RENOVATION OF AN ADDITION TO IMC WING. RECONFIGURATION OF WHS ADMIN AREA. THIS APPLICATION IS FOR DEMOLITION, HAZMAT, FOOTINGS, FOUNDATIONS, SITE WORK PERMIT AND EARLY STRUCTRUAL REVIEW AS AGREE ON WITH THE MOA DURING MEETING 3/8/17. COMPLETED PLANS TO BE SUBMITTED FOR COMPLETE BUILDING PERMIT IN MAY. FULL PAYMENT FOR THE COMPLETED BUILDING PERMIT IS BEING MADE AT THIS TIME TO SIMPLIFY THE APPLICATION AND REVIEW PROCESS. AE
Status:
Closed
Project Name:
Child of Bldg App C17-1344
Review Type:
Fire System
Result:
Correction
Result Date:
10/13/2017 8:17:00 AM
Comments:
Code Section
Review Comment
Status
1
_
Provide code compliant seismic bracing and hanging per 2010 NFPA 13 chapter 9 on new existing piping in the work area. 2012 IBC 903.2.3, 903.3.1.1, 2012 IEBC 804.2.2
2
_
Provide lateral sway bracing calculations for the zone of influence or specific table with pipe length per 2010 NFPA 13 section 9.3.5.3.
Advisory Information: