Permit Number: C17-1802
Permit Type: Commercial Building Permit - None BldgAlter
Address: W 5000 INTERNATIONAL AIRPORT RD Anchorage
Location:
Work Description: INSTALL SUPPORT ANGLES AT ROOF TRUSSES, INSTALL SUPPORT CABLES FROM SUPPORT ANGLES. PATCH CEILING FINISHES. AE
Status: Closed
Project Name: N754 AIRCRAFT DISPLAY ANCHORAGE INTERNATIONAL
Review Type: Structural
Result: Correction
Result Date: 9/15/2017 9:28:12 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:


Reviewed by: Grant Gephardt                                    

Phone: 343-8081                                                                        

Email: GephardtGC@muni.org

 

Permit Manager: Melissa Davidson

Phone: 343-8339

Email: DavidsonMJ@muni.org

 

Permit #: C17-1802

Project: N754 Aircraft Display

Review Number: 397560

Date: 2017 September 15

____________________________________________________________________________________

 

PERMIT STATUS

09/01/2017 – Initial review complete. Comments issued.

09/15/2017 – Second review complete. Additional comments issued.

 

 

ADVISORY COMMENT (NO RESPONSE REQUIRED) 

This review is based on the requirements of the Anchorage Municipal Code (AMC), 2012 International Building Code (IBC), 2012 International Residential Code (IRC) and all adopted references thereto as amended by MOA. The following comments must be addressed before a permit can be issued. The approval of plans and specifications does not permit the violation of the codes, or any federal, state or local regulations.

 

1. STRUCTURAL CALCULATIONS

The structural calculations provided are dated from 2012. The plan provided on sheet S-2 of the calculation package depicts the display in a location that doesn’t match the plans provided on 1/S1. Please provide calculations evaluating the display’s expected position or clarify the intent of the calculations.

 

              09/15/2017 – Comment resolved. New calculations provided.

 

2. STEEL JOISTS

The hanging loads from the existing joists don’t appear to occur at joist panel points. Typically, a concentrated load away from a panel point in excess of 100 lbs usually needs to consider local bending effects on the chord. Has the joist manufacturer been consulted regarding this condition, or were provisions made in the original design for additional concentrated loads?

[Reference: SJI-COSP-2010 § 2.3]

 

3. PLANE ATTACHMENTS

Has the strength of the lifting eye connections to the aircraft been quantified by calculations or testing?

[Reference: AMC § 23.10.104.10]

 

4. TRUSS

From the overall plan 1/S0 and sheet S-2 of the calculation package, it appears (from the end symbols) the truss “C1-13-S” on gridline CCD forms a moment frame. Is this element part of the seismic force resisting system for the building? Do the original construction documents have any prohibitions on adding attachments to members of the SFRS?

 

 

Please provide a written response to the comments and include one copy of additional or revise calculations, and two copies of additional or revised drawings. While not required it is extremely helpful to the reviewer if the response indicates where in the submittal each comments has been addressed.

 

All submittals should be sent to the permit manager.