Permit Number: C17-1802
Permit Type: Commercial Building Permit - None BldgAlter
Address: W 5000 INTERNATIONAL AIRPORT RD Anchorage
Location:
Work Description: INSTALL SUPPORT ANGLES AT ROOF TRUSSES, INSTALL SUPPORT CABLES FROM SUPPORT ANGLES. PATCH CEILING FINISHES. AE
Status: Closed
Project Name: N754 AIRCRAFT DISPLAY ANCHORAGE INTERNATIONAL
Review Type: Fire
Result: Approved
Result Date: 9/20/2017 9:38:01 AM

Comments:

 Code SectionReview CommentStatus
1_Resolved
The aircraft creates an obstruction that shadows protection at the floor level. Please clarify how the existing sprinkler system covers below the obstruction, or clarify that additional heads will be installed.
Reference: IFC Section 903.3.1.1; NFPA 13 Section 8.5.5.3

9/20/17 - Resolved. With the location of the aircraft, there is anticipated protection below the aircraft under the restaurant ceiling lid and no storage will be permitted above. If field conditions are different than what is anticipated, additional coverage may be required //PANILO