Permit Number:
C17-1852
Permit Type:
Commercial Building Permit - None BldgAlter
Address:
W 320 5TH AVE Anchorage
Location:
Work Description:
COMMERCIAL T/I: DEMO EXISTING WALLS & FINISHES; FRAME NEW WALLS , R&R ACOUSTAL CIELING TILES, NEW FLOORING/ PAINT, PLUMBING AND HVAC FOR NEW KITCHEN EQUIPMENT-SM
Status:
Closed
Project Name:
ALASKA CAKE STUDIO AND BOUTIQUE
Review Type:
Fire
Result:
Approved
Result Date:
9/8/2017 12:04:00 PM
Comments:
Code Section
Review Comment
Status
1
_
Resolved
Refer to Sheet G0. The construction type for the 5th Avenue Mall is Type I. Based on previous projects, Type I-B is considered the most applicable. Please revise the code study accordingly.
Reference: IFC Section 105.4.2
2
_
Resolved
Refer to Sheet G0. Please clarify the rating of the fire extinguishers.
Reference: IFC Section 906.3
3
_
Resolved
Please provide information on the construction of the partition walls.
Reference: IFC Section 105.4.2
4
_
Resolved
Please provide information on the freezer panels to show compliance with foam plastic insulation requirements.
Reference: IFC Section 803.7
5
_
Resolved
Plans call for a Type I hood over the kettle and ovens. Please note a separate fire systems permit will be required for the suppression system.
Reference: IFC Section 904.11; AMC 23.45.K103.4