Permit Number: C17-1816
Permit Type: Commercial Building Permit - None BldgAlter
Address: E 800 DIMOND BLVD Anchorage
Location:
Work Description:

TENANT IMPROVEMENT TO AN EXISTING SHELL BUILDING FOR THE RETAIL SALES OF CLOTHING, SHOES AND ACCESSORIES - MJD

GENERAL CONTRACTOR TO PAY FOR INSPECTIONS AT TIME OF PICK UP

Status: Open
Project Name: TORRID CURVE
Review Type: Fire
Result: Approved
Result Date: 9/1/2017 7:11:00 AM

Comments:

 Code SectionReview CommentStatus
1_Resolved
Refer to Sheets T2, A2. Door 107 is noted in the schedule with Group 3 hardware (which does not include a lock), but keynote 6 notes the door to be locked when the tenant space is not occupied. Please note this door is not permitted to be lockable as it is shown to be an exit, and is not considered the main exit. Please clarify the schedule or exiting from the tenant space.
Reference: IFC Section 1008.1.9

8/31/17 - Resolved. Updated schedule deletes Keynote 6 // PANILO