Permit Number: C17-1852
Permit Type: Commercial Building Permit - None BldgAlter
Address: W 320 5TH AVE Anchorage
Location:
Work Description: COMMERCIAL T/I: DEMO EXISTING  WALLS & FINISHES; FRAME NEW WALLS , R&R ACOUSTAL CIELING TILES, NEW FLOORING/ PAINT, PLUMBING AND HVAC FOR NEW KITCHEN EQUIPMENT-SM
Status: Closed
Project Name: ALASKA CAKE STUDIO AND BOUTIQUE
Review Type: Electrical
Result: Correction
Result Date: 8/29/2017 8:35:30 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:



Electrical Comments



 



Reviewed by: David Abuobaid                                                Permit
#: C17-1852



Phone: 343-8333                                                                      Date: 8/29/2017



Fax:     249-7775                                                                     



Email:  AbuobaidDH@muni.org



Permit Manager: Sean McNulty



Phone: 343-8181



Email:  mcnultyss@muni.org



Project: Alaska Cake
Studio (907-272-7753)



____________________________________________________________________________________  



REQUIREMENT OF ELECTRICAL SCOPE OF WORK:



Please provide 100% designed engineered drawing by a
registered professional electrical engineer of the State of Alaska. The design
shall include floor plans, wiring method, home run wiring with type, size of
wires and conduits, over-current protection, accessibility to over-current
protection, existing service load calculations, panel schedules with connected
and demand loads and one-line diagram.