Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: C17-1642
Permit Type: Commercial Building Permit - None BldgAlter
Address: 1076 OCEAN DOCK RD Anchorage
Location:
Work Description:

INSTALLING NEW PIPE SUPPORTS/ RACHS, PUMP PADS WITH NEW PUMPS AND NEW PIPING - MJD

6/29/2017: REMOVE PIPE SUPPORT FROM SCOPE OF WORK - MJD

6/30/2017: READDED PIPE SUPPORT TO SCOPE OF WORK - BWP

Status: Issued
Project Name: EAST OCEAN DOCK TERMINAL
Review Type: Fire
Result: Approved
Result Date: 8/29/2017 9:46:12 AM

Comments:

 Code SectionReview CommentStatus
1_Resolved
Please provide mechanical plans showing the pump layout, shut off locations, and signage.
Reference: IFC Section 105.4.2

8/29/17 - Resolved. Information submitted under the electrical plans for review // PANILO


2_Resolved
Please provide electrical plans showing power distribution, disconnect location(s), classified locations, and signage.
Reference: IFC Section 105.4.2

8/29/17 - Resolved. Plans submitted showing requested information; signage to be coordinated between existing and new components and verified at final inspection // PANILO


3_Resolved
Please note that a separate fire systems permit will need to be secured for modification of the existing foam suppression system. Reference: IFC Section 105.7.1; AMC 23.45.K103.4

8/29/17 - Resolved. Fire systems permit issued under F17-1173 for foam fire suppression system only addresses the temporary piping, A separate permit will be noted as a deferred submittal item. Also note that the fire alarm and detection system will require a separate permit as well // PANILO





Advisory Information:

ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS