Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: X17-1619
Permit Type: Commercial Trade Permit - ChangeOrdr Fire
Address: W 1020 12TH AVE Anchorage
Location:
Work Description: FIRE ALARM PANEL ALTERNATE MEANS AND METHODS-SM
Status: Closed
Project Name: Change Order of F17-1159
Review Type: Fire System
Result: Approved
Result Date: 8/21/2017 10:55:00 AM

Comments:

 Code SectionReview CommentStatus
1_Resolved
Provide a notarized letter on company letter head from the building owner or owners of the property located at 1020 W 12th ave that Mr. Ron Thompson with Scope Permitting & Engineering Services has full legal authority as the Owner Representative to sign documents for permit F17-1159. Or have owner sign the Alternate Means and Methods letter and not Mr. Ron Thompson.

2_Resolved
Fire alarm configuration does not meet the requirements of the 2010 23.8.2.10 for the fire alarm control unit for a subsystem. Please finish filling out the Alternate Design, Materials or Methods of Construction form that has been emailed to you.




Advisory Information:

ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS