Permit Number:
F17-1159
Permit Type:
Commercial Trade Permit - Alteration Fire
Address:
W 1020 12TH AVE Anchorage
Location:
Work Description:
FIRE ALARM WITH 243 DEVICES - MJD
Status:
Closed
Project Name:
INLET TOWER HOTEL AND SUITES
Review Type:
Fire System
Result:
Approved
Result Date:
8/21/2017 10:51:00 AM
Comments:
Code Section
Review Comment
Status
1
AMC 23.10.104.9
Deferral of any submitted items shall have the prior approval of the building official. The registered design professional in responsible charge shall list the deferred submittals on the construction documents for review.
Full electrical drawings that are sealed by an electrical engineer are required for the installation of the CWSI FACP and the 40 each AR-5 repeaters. Drawings must be submitted to MOA Building Safety Electrical Plan Reviewer. Anchorage Municipal Code 23.10.104.1. Fire alarm is required to be on the emergency circuits of the generator per the 2012 IBC 403.4.9.1
2
_
Resolved
Fire alarm configuration does not meet the requirements of the 2010 23.8.2.10 for the fire alarm control unit for a subsystem. Please finish filling out the Alternate Design, Materials or Mehtods of Construction form that has been emailed to you.
3
AMC 23.10.104.9
Deferral of any submitted items shall have the prior approval of the building official. The registered design professional in responsible charge shall list the deferred submittals on the construction documents for review.
Resolved
Fire Alarm Installation Affidavit to be filled out and submitted with the electrical permit deferred submittial as per verbal agreement with Lars Swenson with Yukon Fire Protection