Reviewed by: Grant Gephardt
Phone: 343-8081
Email: GephardtGC@muni.org
Permit Manager: Melissa Davidson
Phone: 343-8339
Email: DavidsonMJ@muni.org
Permit #: C17-1802
Project: N754 Aircraft Display
Review Number: 395900
Date: 2017 September 1
____________________________________________________________________________________
PERMIT STATUS
09/01/2017 – Initial review complete. Comments issued.
Advisory Comment (no response required): This review is based on the requirements of the Anchorage Municipal Code (AMC), 2012 International Building Code (IBC), 2012 International Residential Code (IRC) and all adopted references thereto as amended by MOA. The following comments must be addressed before a permit can be issued. The approval of plans and specifications does not permit the violation of the codes, or any federal, state or local regulations.
1. STRUCTURAL CALCULATIONS
The structural calculations provided are dated from 2012. The plan provided on sheet S-2 of the calculation package depicts the display in a location that doesn’t match the plans provided on 1/S1. Please provide calculations evaluating the display’s expected position or clarify the intent of the calculations.
Please provide a written response to the comments and include one copy of additional or revise calculations, and two copies of additional or revised drawings. While not required it is extremely helpful to the reviewer if the response indicates where in the submittal each comments has been addressed.
All submittals should be sent to the permit manager.