Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: C17-1802
Permit Type: Commercial Building Permit - None BldgAlter
Address: W 5000 INTERNATIONAL AIRPORT RD Anchorage
Location:
Work Description: INSTALL SUPPORT ANGLES AT ROOF TRUSSES, INSTALL SUPPORT CABLES FROM SUPPORT ANGLES. PATCH CEILING FINISHES. AE
Status: Closed
Project Name: N754 AIRCRAFT DISPLAY ANCHORAGE INTERNATIONAL
Review Type: Fire
Result: Correction
Result Date: 8/22/2017 8:39:20 AM

Comments:

 Code SectionReview CommentStatus
1_
The aircraft creates an obstruction that shadows protection at the floor level. Please clarify how the existing sprinkler system covers below the obstruction, or clarify that additional heads will be installed.
Reference: IFC Section 903.3.1.1; NFPA 13 Section 8.5.5.3




Advisory Information:

ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS