Permit Number: C17-1643
Permit Type: Commercial Building Permit - None BldgNew
Address: 1076 OCEAN DOCK RD Anchorage
Location:
Work Description:

INSTALLING NEW EQUIPMENT FOUNDATION 668 SQFT 11B UTILITY, PIPE RACKS AND PIPING, NEW TRUCK RACK FRAME AND FOUNDATION AND A NUMBER OF KIOSKS - MJD

6/29/2017: REMOVE PIPE SUPPORTS FROM SCOPE OF WORK - MJD

6/30/2017: READDED PIPE SUPPORT TO SCOPE OF WORK - BWP

Status: Issued
Project Name: WEST OCEAN DOCK TERMINAL
Review Type: Structural
Result: Correction
Result Date: 8/2/2017 2:22:11 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

Reviewed by: Gephardt, Grant                                                

Phone: 343-8081                                                                      

Email: GephardtGC@muni.org

 

Permit Manager: Davidson, Melissa

Phone: 343-8339

Email: DavidsonMJ@muni.org

 

Permit #: C17-1643

Project: West Ocean Dock Terminal

Review Number: 393296

Date: 2017 August 2

____________________________________________________________________________________

 

PERMIT STATUS

08/02/2017 – Initial review complete. Comments issued.

 

Advisory Comment (no response required):  This review is based on the requirements of the Anchorage Administrative Code (AAC), 2012 International Building Code (IBC), 2012 International Residential Code (IRC) and all adopted references thereto as amended by MOA. The following comments must be addressed before a permit can be issued. The approval of plans and specifications does not permit the violation of the codes, or any federal, state or local regulations.

 

1. CONSTRUCTION DOCUMENTS

The structural drawings are stamped “NOT FOR CONSTUCTION”. Is this the intent when applying for a building permit?

[Reference: AAC § 23.10.104.10.1]

 

2. TRUCK LOADING RACK FOUNDATION

The provided geotechnical report from 2015 seems to indicate the existing canopy is supported by a pile foundation. The 2004 report indicates the presence of frost susceptible soils and high groundwater table at the site. The new canopy appears to use a shallow mat foundation. Please justify the lack of frost protection for the foundation of the new truck loading rack structure.

[Reference: IBC 2012 § 1809.5, AAC § 23.15.1809.5]

 

3. SPECIAL INSPECTIONS

Please provide a letter from the Owner indicating who they will be hiring to provide the special inspections for this project. The special inspectors must be licensed by the Municipality of Anchorage in the types of inspections to be performed.

[Reference: IBC 2012 § 1704.2, AAC § 23.15.1703.7]

 

Please provide a written response to the comments and include one copy of additional or revise calculations, and two copies of additional or revised drawings. While not required it is extremely helpful to the reviewer if the response indicates where in the submittal each comments has been addressed.

 

All submittals should be sent to the permit manager.