Permit Number: C17-1643
Permit Type: Commercial Building Permit - None BldgNew
Address: 1076 OCEAN DOCK RD Anchorage
Location:
Work Description:

INSTALLING NEW EQUIPMENT FOUNDATION 668 SQFT 11B UTILITY, PIPE RACKS AND PIPING, NEW TRUCK RACK FRAME AND FOUNDATION AND A NUMBER OF KIOSKS - MJD

6/29/2017: REMOVE PIPE SUPPORTS FROM SCOPE OF WORK - MJD

6/30/2017: READDED PIPE SUPPORT TO SCOPE OF WORK - BWP

Status: Issued
Project Name: WEST OCEAN DOCK TERMINAL
Review Type: Fire
Result: Correction
Result Date: 8/2/2017 7:50:16 AM

Comments:

 Code SectionReview CommentStatus
1_
Refer to Sheet S-002. Please clarify the area of the existing truck rack canopy.
Reference: IFC Section 105.4.2; IBC Section 503.1


2_
Refer to Sheet S-104. Please provide a code study for the break room.
Reference: IFC Section 105.4.2


3_
Please provide mechanical plans showing the pump layout, shut off locations, and signage.
Reference: IFC Section 105.4.2


4_
Please provide electrical plans showing power distribution, disconnect location(s), classified locations, and signage.
Reference: IFC Section 105.4.2


5_
Please note that a separate fire systems permit will need to be secured for modification of the existing foam suppression system. Reference: IFC Section 105.7.1; AMC 23.45.K103.4