Permit Number: C17-1576
Permit Type: Commercial Building Permit - None Reroof
Address: 4150 AIRCRAFT DR Anchorage
Location:
Work Description:

RE-ROOF:   REMOVE AND REPLACE EXISTING ROOFING ASSEMBLY.  REPLACE EXISITNG ROOF DRAINS, NEW PARAPET WALLS. (BUILDING 2)  UPGRADE EXISTING UNIT HEATERS.  AE

****FOLDER CREATED  PLANS INSIDE****


Status: Closed
Project Name: WARM STORAGE BUILDING HEATER REPLACE BLDG 1
Review Type: Structural
Result: Correction
Result Date: 7/18/2017 9:06:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:



Structural Comments



 



Reviewed by: Hellman, Becky A.                                         Permit
#: C17-1576



Phone: 343-8237                                                                                 
  First Review



Fax: 249-7400                                                                   
Date: 7-18-17



Email: hellmanba@muni.org



Permit Manager: Earp,
Andrew



Phone: 343-8338



Email: EarpAL@muni.org



Project: Anchorage
International Airport -4150 Aircraft – State of Alaska – Warm Storage BLDG 1



____________________________________________________________________________________



Plan review
comments:



 



1.  This review is a
code compliance review based on the requirements of the 2012 International
Building Code (IBC) and all adopted references thereto as amended by the
Municipality of Anchorage in the Anchorage Municipal Code (AMC) Title 23.  This review does not permit the violation of
the building codes, nor any federal, state, or municipal regulation.



 



2. Please provide a
full set of plans, the writing is required to be a minimum of 3/32” for the
field set per policy AG 39.



 



3. See the codes and
standards. Sheet G1.  The MOA is
currently under the 2012 codes and were under this version of the code when the
plans were stamped; please update the code referenced for this project to meet
the current version of adopted codes.



 



4.  Engineer of record is responsible for the
attachment of the parapet as seen on sheet A1 and A2; since he is responsible for
the details that references his design, the pages shall be stamped. 



Also, in the details
(3, 4, 5, and 7) that are on sheet A2 that shows added parapets, will the
attachment of the parapet be the same as detail 6, if so, please state typical
for all details to follow this attachment. 



 



5.  See the plan on sheet A1.  Around the raised framing are referenced
details that are on sheet A2, but A1 is noted, please revise reference.



 



6.  See the details on sheet S3.  Per the NDS 10.1.4; methods of analysis and
test data for establishing reference design values for connections made with
more than one type of fasteners have not been developed.  Referenced design values and design values
adjustments for mixed fastener connections shall be based on tests or other
analysis.  Please revise the design of these
added connection to consider equal type fasteners for load sharing per this
code section.



 



Address all comments above to complete the permit process.  Please provide corresponding letter that
describes how comments have been addressed and where on the plans the changes
have occurred.  Any additional
information that is provided to address the above comments could result in
additional comments based on the new information provided for review.   All
submittals should be sent or given to the permit manager of this project.