Register
My Neighborhood
Jobs
Contact Us
Home
Residents
Businesses
Government
Visitors
Departments
Public Safety
Transportation
Recreation
ePay
Maps
Services A-Z
Muni.org
>
Departments
>
Development Services
> Permit Information & Inspection Request
Click Here To Go Back To Permit Information
Permit Number:
F17-1104
Permit Type:
Commercial Trade Permit - Alteration Fire
Address:
W 320 5TH AVE Anchorage
Location:
Work Description:
2ND FLOOR COMMON AREA- FIRE ALARM RETROFIT- 184 DEVICES
Status:
Issued
Project Name:
Review Type:
Fire System
Result:
Approved
Result Date:
6/12/2017 2:29:00 PM
Comments:
Code Section
Review Comment
Status
1
_
Resolved
(1) Pull station required at the entrance from the mall public area to the horizontal 2 hour exit. (2) back corridor ceilings are over 10 feet and ceiling strobes need to be derated (3) strobe coverage in complete (4) smoke detectors incomplete coverage (4) voltage drop cals shall start at 20.4 volts (5) amperage for the strobes being used it the 24 volt amperage, need to use the 16 volt DC amperage for the strobes and speaker strobes (6) provide load calc for each audio amplifier (7) plan review stopped.
Advisory Information:
ADA Compliance
Privacy Statement & Disclaimer
Employee Search
eNewsletter
RSS
OFFICIAL WEB SITE OF THE MUNICIPALITY OF ANCHORAGE, ALASKA
632 West 6th Avenue, Anchorage, Alaska 99501