Permit Number:
F17-1118
Permit Type:
Commercial Trade Permit - Alteration Fire
Address:
1200 AIRPORT HEIGHTS DR Anchorage
Location:
Work Description:
FIRE SPRINKLER, 69 DEVICES-SM
Status:
Closed
Project Name:
CHILD OF C17-1399
Review Type:
Fire System
Result:
Correction
Result Date:
5/31/2017 10:19:00 AM
Comments:
Code Section
Review Comment
Status
1
_
Provide sprinkler coverage in room 120
2
_
Provide sprinkler coverage in room 127
3
_
Special inspections required for post install anchors in concrete and masonary perm 2012 IBC Table 1705.3 #4. Provide special inspectors report at fire sprinkler final
4
_
Provide on plans installation details to include installation depth and calculations on post installed anchors.
Advisory Information: