Permit Number:
F17-1104
Permit Type:
Commercial Trade Permit - Alteration Fire
Address:
W 320 5TH AVE Anchorage
Location:
Work Description:
2ND FLOOR COMMON AREA- FIRE ALARM RETROFIT- 184 DEVICES
Status:
Issued
Project Name:
Review Type:
Fire System
Result:
Correction
Result Date:
5/25/2017 3:16:00 PM
Comments:
Code Section
Review Comment
Status
1
_
(1) Pull station required at the entrance from the mall public area to the horizontal 2 hour exit. (2) back corridor ceilings are over 10 feet and ceiling strobes need to be derated (3) strobe coverage in complete (4) smoke detectors incomplete coverage (4) voltage drop cals shall start at 20.4 volts (5) amperage for the strobes being used it the 24 volt amperage, need to use the 16 volt DC amperage for the strobes and speaker strobes (6) provide load calc for each audio amplifier (7) plan review stopped.