Permit Number: F17-1075
Permit Type: Commercial Trade Permit - Alteration Fire
Address: W 320 5TH AVE Anchorage
Location:
Work Description:

DEVICES:  (7)   STANDALONE F.ALARM.   AE DO NOT ISSUE PERMIT UNTIL SIMON 5TH AVE MALL AND SUNGLASSES HUT PAY THEIRF FINES PER BART 5/9/2017

FEES TO BE PAID FOR 3RD OFFENSE NOPR PER BART MEINHART- NOTICE DATED 4/13/17. 

CONTRACTOR PAID $3000.00 5/8/17.  AE

CONTRACTOR PAID ADDITIONAL FEES OF $4000.00 5/12/17.BWP

Status: Closed
Project Name: SUNGLASS HUT- 5TH AVE MALL STE E60
Review Type: Fire System
Result: Approved
Result Date: 5/8/2017 7:44:00 AM

Comments:

 Code SectionReview CommentStatus
1_Transfer
NOPR (Notice of Permit Required) to be issued for starting work before permit applied for and approved - contractor installed equipment before permit was applied for on 4/10/2017 - Megawatt Electric, ATS Alaska, Simon Properties, Sunglass Hut.

2_Resolved
Fire Alarm Installation Affidavit required before the permit can be approved.

3_Resolved
Installer Kent Liska does not have at State of Alaska Electrical Administrators License or Fire Alarm permit for installation of fire alarm systems

4_Resolved
Drawings are not to scale. Scale bar provide but not standard scale of 1/8, 3/16, 1/4 inch appears to be like 1.125 inches equal 5 feet which is not an approved drafting scale size.

5_Resolved
How is the BPS being activated?

6_Transfer
Mall requires speaker strobes and not horn strobes that are being installed in this unit........5-8-2017 to be complete on future phase....Bart Meinhardt

7_Transfer
what audio circuit is being user for speakers?.......5-8-2017 to be complete on future phase....Bart Meinhardt

8_Transfer
No calcs provided for AUDIO circuit.......5-8-2017 to be complete on future phase....Bart Meinhardt

9_Resolved
No battery calcs provided for BPS

10_Resolved
No voltage drops provided for BPS

11_Resolved
No smoke detector provided over BPS - some type of detector in room, but not specified.

12_Resolved
No Riser diagram provide for the SLC, Audio or NAC's

13_Transfer
Retro Electrical permit required for the installation of the BPS's 120 VAC electrical

14_Resolved
Fire alarm emergency voice evacuation system shall be on Emergency Power Loads per 2009 IBC 403.4.8.1 and 2012 IBC 403.4.9.1