Permit Number:
C17-1399
Permit Type:
Commercial Building Permit - None BldgAlter
Address:
1200 AIRPORT HEIGHTS DR Anchorage
Location:
Work Description:
FRAMING, SHEETROCK, TAPE AND PAINT, CASEWORK, ELECTRICAL, PLUMBING, AND MECHANICAL. AE
Status:
Closed
Project Name:
ALASKA REGIONAL MOB E STE 140 TANIANA DAYCARE
Review Type:
Fire
Result:
Correction
Result Date:
5/23/2017 4:47:56 PM
Comments:
Code Section
Review Comment
Status
1
_
Refer to Sheet A0.1, A2.1. The code study notes the occupancy as Group E. As there are toddler care areas (age <2-1/2 years), direct exiting from this space to the exterior is required. Please clarify the occupancy as Group I-4, or provide compliant direct egress from the space.
Reference: IFC Section 105.4.2; IBC Section 308.6.1
2
_
Refer to Sheet A2.1. The kitchen area may require a Type I hood with fire suppression, dependent on the number of children the facility is licensed for. Please provide a copy of the State of Alaska Childcare License. If the license is for more than 80 children, a Type I hood with fire suppression is required. If the license is 80 or less, please provide a copy of the menu for foods to be prepared. Foods that will produce grease-laden vapors when cooked will require a Type I hood with fire suppression.
Reference: IFC Section 904.11; IMC Section 507.2.1; AFD Policy #08-002
3
_
Please clarify fire extinguisher coverage for the north and south areas of the tenant space. The FE/FEC shown is beyond the 75 ft. travel distance to these areas (Gym, Preschool 1).
Reference: IFC Section 906.3