Drawing A600, Door Schedule; Are the Toilet Room Doors shown as 028 and 029 intended to not be 20 minute Fire Resistant rated per IBC Table 1018.1? Refer to Drawing A101a, Main Level Floor Plan - Area A; Drawing A020, Code Plans, Section 1, 1st Floor Code Plan; and preceding comment 6. RESOLVED. The design appears to comply with the IBC Figure 1018.6(1), "Corridor Continuity-Example 1" as shown in the Commentary.
Drawing A600, Door Schedule; Is the Work Room Door shown as 036 intended to not be 20 minute Fire Resistant rated per IBC Table 1018.1? Refer to Drawing A101a, Main Level Floor Plan - Area A; Drawing A020, Code Plans, Section 1, 1st Floor Code Plan; and preceding comment 6. RESOLVED. The design appears to comply with the IBC Figure 1018.6(1), "Corridor Continuity-Example 1" as shown in the Commentary.
Drawing A600, Door Schedule; Is the Electrical Room Door shown as 040a inadvertently missing from the Door Schedule. Additionally, is this Electrical Room Door shown as 040a intended to not be 20 minute Fire Resistant rated per IBC Table 1018.1? Refer to Drawing A101a, Main Level Floor Plan - Area A; Drawing A020, Code Plans, Section 1, 1st Floor Code Plan; and preceding comment 6. RESOLVED.
Drawing A600, Door Schedule; Are the Stair Exit Enclosure Doors shown as 050b and 051b intended to not be 90 minute Fire Resistant rated per IBC Section 1022.7? Refer to Drawing A101a, Main Level Floor Plan - Area A; Drawing A101b, Main Level Floor Plan - Area B; and Drawing A020, Code Plans, Section 1, 1st Floor Code Plan. Please clarify. NOT RESOLVED. Note that my earlier comment referenced the wrong code section in error; it should not be 1027.7, but rather 1022.7. It is now corrected above. The two Doors may not require a rating if you can show alternate compliance with this IBC Section 1022.7. RESOLVED. These two Doors now indicate a 45 minute Fire-Resistance Rating which is in compliance with the applicable IBC Section 1022.7.
Drawing A600, Door Schedule; The Door Schedule includes a Closet Door shown as 052. Is the Closet Door shown as 052 inadvertently missing from the Plans? Refer to Drawing A101a, Main Level Floor Plan - Area A and Drawing A101b, Main Level Floor Plan - Area B. RESOLVED.
Drawing A600, Door Schedule; Is the Stair Exit Enclosure Door shown as 550 intended to not be 90 minute Fire Resistant rated per IBC Section 1022.7? Refer to Drawing A105, Roof Plan. Please clarify. NOT RESOLVED. Note that my earlier comment referenced the wrong code section in error; it should not be 1027.7, but rather 1022.7. It is now corrected above. The Door may not require a rating if you can show alternate compliance with this IBC Section 1022.7. RESOLVED. This Door does not require a rating and need not show compliance with IBC Section 1022.7.
Drawing A101a, Main Level Floor Plan - Area A; Drawing A101b, Main Level Floor Plan - Area B; and Drawing A020, Code Plans, Section 1, 1st Floor Code Plan; Since the Courtyard is not sufficiently far enough away from the hotel, please verify that Door 071 has the required egress width. Two doors may be required, unless you can show the adequacy of this exit. Please clarify. RESOLVED. This satisfies the minimum exiting requirements.