Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: X17-1099
Permit Type: Commercial Building Permit - ChangeOrdr BldgNew
Address:
Location:
Work Description: Change order to S/A/P/M/E/F/Z - BWP
Status: Closed
Project Name: Change Order of Bldg App C15-1806
Review Type: Architectural
Result: Correction
Result Date: 5/15/2017 3:39:00 PM

Comments:

 Code SectionReview CommentStatus
1_
Please refer to Fire Plan Review comments 2, 3, 4, & 5.  These also apply to Architectural Plan Review; please route their responses to Architectural Plan Review.  NOT YET RESOLVED.  Awaiting Fire Plan Review Approval.  STILL NOT YET RESOLVED.  Awaiting Fire Plan Review Approval for the two remaining open comments.

2_
Drawing A101a, Main Level Floor Plan - Area A; The Door located near column lines H/11 is labeled as 017 which is not on Door Schedule Drawing A600.  It appears that it is mislabeled and should be Door 071 to co-ordinate with Door Schedule Drawing A600 and Enlarged Courtyard Drawing A052, Detail 8.  RESOLVED. 

3_
Drawing A600, Door Schedule; Is the Door shown as 013 intended to be shown as Door 014?  Refer to Drawing A101a, Main Level Floor Plan - Area A.  RESOLVED.

4_
Drawing A600, Door Schedule; Are the Doors shown as 015c and 015d have their numbers flip flopped? I believe they are intended to be shown as Doors 015d and 015c (just the opposite of as shown on the plans)?  Refer to Drawing A101a, Main Level Floor Plan - Area A.  RESOLVED.

5_
Drawing A600, Door Schedule;  Is the Door shown as 016 (Electrical) still indicated on the plans? Refer to Drawing A101a, Main Level Floor Plan - Area A and Drawing A101b, Main Level Floor Plan - Area B.  I cannot find Door 016 on these plans.  RESOLVED.

6_
Drawing A020, Code Plans, Section 1, 1st Floor Code Plan;  Please identify the continuity compliance with regard to the requirements of IBC Section 1018.6.  RESOLVED.  The design appears to comply with the IBC Figure 1018.6(1), "Corridor Continuity-Example 1" as shown in the Commentary.

7_

Drawing A600, Door Schedule; Are the Toilet Room Doors shown as 028 and 029 intended to not be 20 minute Fire Resistant rated per IBC Table 1018.1?  Refer to Drawing A101a, Main Level Floor Plan - Area A; Drawing A020, Code Plans, Section 1, 1st Floor Code Plan; and preceding comment 6.  RESOLVED.  The design appears to comply with the IBC Figure 1018.6(1), "Corridor Continuity-Example 1" as shown in the Commentary.



8_

Drawing A600, Door Schedule; Is the Work Room Door shown as 036 intended to not be 20 minute Fire Resistant rated per IBC Table 1018.1?  Refer to Drawing A101a, Main Level Floor Plan - Area A; Drawing A020, Code Plans, Section 1, 1st Floor Code Plan; and preceding comment 6.  RESOLVED.  The design appears to comply with the IBC Figure 1018.6(1), "Corridor Continuity-Example 1" as shown in the Commentary.



9_

Drawing A600, Door Schedule; Is the Electrical Room Door shown as 040a inadvertently missing from the Door Schedule.   Additionally, is this Electrical Room Door shown as 040a intended to not be 20 minute Fire Resistant rated per IBC Table 1018.1?  Refer to Drawing A101a, Main Level Floor Plan - Area A; Drawing A020, Code Plans, Section 1, 1st Floor Code Plan; and preceding comment 6.  RESOLVED.



10_

Drawing A600, Door Schedule; Are the Stair Exit Enclosure Doors shown as 050b and 051b intended to not be 90 minute Fire Resistant rated per IBC Section 1022.7?  Refer to Drawing A101a, Main Level Floor Plan - Area A; Drawing A101b, Main Level Floor Plan - Area B; and Drawing A020, Code Plans, Section 1, 1st Floor Code Plan.  Please clarify.  NOT RESOLVED.  Note that my earlier comment referenced the wrong code section in error; it should not be 1027.7, but rather 1022.7.  It is now corrected above. The two Doors may not require a rating if you can show alternate compliance with this IBC Section 1022.7.  RESOLVED.  These two Doors now indicate a 45 minute Fire-Resistance Rating which is in compliance with the applicable IBC Section 1022.7.



11_

Drawing A600, Door Schedule; The Door Schedule includes a Closet Door shown as 052.  Is the Closet  Door shown as 052 inadvertently missing from the Plans?  Refer to Drawing A101a, Main Level Floor Plan - Area A  and Drawing A101b, Main Level Floor Plan - Area B.  RESOLVED.



12_
Drawing A600, Door Schedule; Are the Doors shown as 226a and 226b correctly numbered? I believe they are intended to be shown as Doors 224a and 224b (to match numbers shown on the plans)?  Refer to Drawing A102a, Second Level Floor Plan - Area A.  RESOLVED.

13_
Drawing A600, Door Schedule; Is the Door shown as 443 mislabeled? Instead of Communications, I believe that Door 443  is intended to be shown as Electrical (to match the room name shown on the plans)?  Refer to Drawing A104a, Fourth Level Floor Plan - Area A.  RESOLVED.

14_

Drawing A600, Door Schedule; Is the Stair Exit Enclosure Door shown as 550 intended to not be 90 minute Fire Resistant rated per IBC Section 1022.7?  Refer to Drawing A105, Roof Plan.  Please clarify.  NOT RESOLVED.  Note that my earlier comment referenced the wrong code section in error; it should not be 1027.7, but rather 1022.7.  It is now corrected above.  The Door may not require a rating if you can show alternate compliance with this IBC Section 1022.7.  RESOLVED.  This Door does not require a rating and need not show compliance with IBC Section 1022.7.



15_

Drawing A101a, Main Level Floor Plan - Area A; Drawing A101b, Main Level Floor Plan - Area B; and Drawing A020, Code Plans, Section 1, 1st Floor Code Plan;  Since the Courtyard is not sufficiently far enough away from the hotel, please verify that Door 071 has the required egress width.  Two doors may be required, unless you can show the adequacy of this exit.  Please clarify.  RESOLVED.  This satisfies the minimum exiting requirements.



16_
The Elevator Openings on the first floor are not provided with Smoke Doors.  Since the building is provided with a full NFPA 13 Sprinkler System, please verify that your intent is to utilize IBC Section 708.14.1, exception 1.  RESOLVED.




Advisory Information:

ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS