Register
My Neighborhood
Jobs
Contact Us
Home
Residents
Businesses
Government
Visitors
Departments
Public Safety
Transportation
Recreation
ePay
Maps
Services A-Z
Muni.org
>
Departments
>
Development Services
> Permit Information & Inspection Request
Click Here To Go Back To Permit Information
Permit Number:
C17-1289
Permit Type:
Commercial Building Permit - None BldgAlter
Address:
4140 B ST Anchorage
Location:
Work Description:
STRUCTURAL SUPPORT FOR GCI ANTENNA EQUIPMENT (STRUCTURAL ONLY). AE
Status:
Open
Project Name:
ER 14084 TOWER
Review Type:
Fire
Result:
Approved
Result Date:
4/13/2017 4:18:46 PM
Comments:
Code Section
Review Comment
Status
Advisory Information:
No final fire inspection required // PANILO
ADA Compliance
Privacy Statement & Disclaimer
Employee Search
eNewsletter
RSS
OFFICIAL WEB SITE OF THE MUNICIPALITY OF ANCHORAGE, ALASKA
632 West 6th Avenue, Anchorage, Alaska 99501