Permit Number: C17-1119
Permit Type: Commercial Building Permit - None BldgAlter
Address: E 800 DIMOND BLVD Anchorage
Location:
Work Description: TENANT IMPROVEMENT TO INCLUDE PLUMBING, MECHANICAL, ELECTRICAL.   AE
Status: Closed
Project Name: DAVE AND BUSTERS
Review Type: Fire
Result: Correction
Result Date: 4/19/2017 10:18:46 AM

Comments:

 Code SectionReview CommentStatus
1_
Refer to Sheet T1.1. General Note L calls for fire extinguisher locations to be confirmed by Fire Marshal. Please provide location(s) and class/rating(s) on the plans for verification.
This item may be deferred.
Reference: IFC Section 906.3; AMC 23.10.104.11

4/19/17 - Not resolved. The plan on Sheet A0.2 notes the fire extinguisher coverage as "Ordinary Hazard" per IFC Table 906.3(1). Under ordinary hazard, each unit of A protects 1,500 sq. ft. of floor area. Over the 47,000 sq. ft. of tenant space, this requires a minimum of 32 units of A. Only 14A is shown on the plans. In addition, the coverage of Rooms 101, 107, 114 exceed the 75 ft. maximum travel distance. Please clarify coverage.


2_
Refer to Sheets MP0.1a, MP0.1b, M1.1a thru M3.2, ESP1.0, E0.1 thru E1.6b, E2.0a thru E4.2.
Please provide plans sealed by the registered design professional.
Reference: IFC Section 105.4.2; AS 08.48.221

4/19/17 - Not resolved. No information provided this review // PANILO


3_
ADVISORY
Refer to Sheet FA1.0. Please note that the tenant will not be permitted to have a fire alarm control panel separate from the rest of the mall building; response provided to firedynamics/Henderson Engineering Inc.
Reference: IFC Section 105.4.2


4_
ADVISORY
Refer to Sheet FA1.0. As the fire alarm system is required to have emergency voice/alarm capability, it is advisable that acoustic modeling of the tenant spaces be provided to the fire alarm designer to facilitate proper design of system to meet intelligibility requirements of NFPA 72.
Reference: IFC Section 907.2; NFPA 72 Section 18.4.10, D.1.4


5_
ADVISORY
Refer to Sheet SP1.0. The protection criteria notes the sprinkler density at less than 0.2 gpm/sq.ft. Please note that under previous agreements, the entirety of the mall shall be covered with a sprinkler density required for mercantile space not less than 0.2 gpm/sq.ft.
Reference: IFC Section 105.4.2