Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: C16-1597
Permit Type: Commercial Building Permit - None BldgAlter
Address: W 239 4TH AVE Anchorage
Location:
Work Description: Add helipad to top of building with stairs on the exterior of building - BWP
CANCELLED PER KAYLI ON 09-02-2021 - JRS
Status: Cancelled
Project Name: THE LOFT DOWNTOWN HELIPAD
Review Type: Structural
Result: Correction
Result Date: 3/16/2017 10:09:11 AM

Comments:

 Code SectionReview CommentStatus
1AMC 23.10.104.8.1Construction documents shall be of sufficient clarity to indicate the location, nature, and extent of the work proposed and show in detail that the work will conform to the provisions of this code.
Please resolve non-combustible construction requirement per IBC Section 412.7.2.

2AMC 23.10.104.8.1Construction documents shall be of sufficient clarity to indicate the location, nature, and extent of the work proposed and show in detail that the work will conform to the provisions of this code.
The proposed helistop location is not in conformance with the location identified in the FAA permit. Please provide confirmation from FAA with no objection to the new location.

3_
The FAA permit notes the design aircraft as a Bell 206B-3 helicopter. Available specifications for this aircraft note the maximum take-off weight as 3,200-3,350 lbs. As this exceeds the 3,000 lbs design limit per IBC for 40 psf, the design load of the helipad and supporting structure is 60 psf. Please provide revised design accordingly.
Reference: IBC Section 1607.6 Item 1


4_
The proposed design does not address point considerations as required by IBC. Please provide revised calculations accordingly.
Reference: IBC Section 1607.6 Items 2 and 3


5AMC 23.10.104.8.1Construction documents shall be of sufficient clarity to indicate the location, nature, and extent of the work proposed and show in detail that the work will conform to the provisions of this code.
The proposed design does not address localized lateral stability of the helipad framing. Please provide for review.

6AMC 23.10.104.8.1Construction documents shall be of sufficient clarity to indicate the location, nature, and extent of the work proposed and show in detail that the work will conform to the provisions of this code.
The provided design does not include any connections for the helipad, nor any design for those connections, including the bracket detail 1/S1.0. Please provide for review.

7AMC 23.10.104.8.1Construction documents shall be of sufficient clarity to indicate the location, nature, and extent of the work proposed and show in detail that the work will conform to the provisions of this code.
Please provide design and construction details for the stairs and walkway shown on Sheet A2.1.




Advisory Information:

PERMIT STATUS
3/16/2017 - Please provide response to structural comments.
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS